1. Safety Instructions

  • Only qualified professionals may perform work; non-professionals are strictly prohibited from unauthorized operation, inspection, or maintenance of electrical cabinets.
  • After power-off, voltage must be verified, warning tags hung, and locks applied; confirm no power before construction to prevent accidental energization.
  • After equipment power-off, wait until all electrical component indicator lights or displays are extinguished before operating, to eliminate residual voltage electric shock risk.
  • Live work should not be performed unless necessary; if live work is essential, a dedicated person must accompany the operation.

2. Main Risks of High Temperature to Electrical Control Cabinets

Rotomolding Machines operate in environments with both oven radiant heat and summer ambient high temperatures. Electrical control cabinets face the following primary risks during summer operation:

Risk Item

Cause

Consequence

Excessive cabinet internal temperature

Ambient temperature combined with internal component heat generation; insufficient heat dissipation

Inverter derating or shutdown; PLC unresponsive or abnormal operation; accelerated contactor contact oxidation

Cooling fan failure

Filter mesh blockage or fan bearing insufficient lubrication causing jamming

Cabinet temperature runs out of control

Humidity / condensation

Rapid humidity rise after heavy summer rain; temperature differential causing condensation

Terminal corrosion, circuit board corrosion, reduced insulation performance

Cable connector overheating

High ambient temperature reduces conductor current-carrying capacity; increased contact resistance

Connector melting, phase-to-phase short circuit; in severe cases, fire

Dust accumulation

High summer ventilation volume increases external dust ingress

Heat sink blockage, circuit board dust-induced short circuit

 

3. Daily Precautions

3.1 In-Operation Inspection (Each Shift)

  • Monitor cabinet internal temperature: should not exceed 45 °C; cabinets equipped with inverters or PLCs are recommended to stay within 40 °C.
  • Confirm cooling fans and cabinet-top exhaust fans operate normally without abnormal noise.
  • Check cabinet door sealing strip integrity; confirm the cabinet door is closed and locked.
  • Confirm no less than 800 mm of ventilation space is reserved at the front and rear of the cabinet; no debris may be stacked around it.
  • After heavy rainfall, open the cabinet door to check for water ingress or condensation traces.

3.2 Key Component Inspection

Component

Inspection Points

Inverter

Use an infrared thermometer per shift to check heat sink temperature; should not exceed 80 °C. If overheating faults occur frequently, stop the machine to clean air ducts and heat sinks.

Contactor / Relay

Check whether contact action shows aging and whether there is continuous buzzing. Summer accelerates contact oxidation; abnormal sound usually indicates an aging risk.

PLC / HMI

When ambient temperature exceeds 50 °C, some models may become unresponsive or operate abnormally; ensure cabinet internal temperature stays within the allowable range.

Switching Power Supply

High temperature significantly shortens electrolytic capacitor lifespan; summer is a peak period for switching power module failures; prioritize inspection.

Terminal Block

Focus on inspecting high-current circuit terminals, including the main motor circuit and heating circuit. Check terminals and nearby insulation for discoloration, scorching, or odor.

 

3.3 During Shutdown

  • For extended shutdown (over 2 hours), disconnect the main power supply.
  • During thunderstorms, disconnect the main power to prevent lightning surges from entering through power lines and damaging PLCs, inverters, and other sensitive equipment.
  • Clean the cabinet exterior and keep heat dissipation windows unobstructed.

4. Summer Special Maintenance (Recommended Weekly)

4.1 Filter Mesh Cleaning

The electrical cabinet heat dissipation port filter cotton blocks external dust from entering; maintenance should be intensified in summer.

  • Remove the filter cotton and use compressed air from inside to outside to clear accumulated dust. Do not reinstall filter cotton before it is completely dry after washing.
  • When dust accumulation is severe or oily, soak and clean with a neutral detergent, then thoroughly dry before reinstalling.
  • Replace immediately if the filter mesh is found damaged or deformed.

4.2 Cooling Fan

  • After power-off, manually turn the fan blades to check for flexible rotation and no jamming.
  • Use dry compressed air to remove dust from fan blades and air ducts.

4.3 Electrical Connection Tightening (Operate in Power-Off State)

Summer ambient temperature fluctuates significantly, and thermal expansion/contraction effects occur frequently, making electrical connectors prone to loosening.

Inspection Position

Tightening Method

Main breaker inlet/outlet terminals

Use a torque wrench to recheck one by one.

Contactor and relay terminals

Use a screwdriver to inspect and tighten one by one.

Inverter input/output terminals

Use a torque wrench to recheck; also verify shield layer grounding reliability.

Main circuit terminals

This circuit carries large current and high thermal stress; should be a priority inspection item.

Grounding busbar

Confirm all grounding wires are connected firmly; grounding busbar surface free of oxidation.

 

4.4 Insulation Testing

  • Use a 500 V megohmmeter to measure main circuit-to-ground insulation resistance; should not be less than 1 MΩ.
  • In humid environments, prioritize testing main circuit-to-ground insulation.
  • When insulation resistance is found to decrease, disconnect power and use hot air or a moisture-proof heater for drying.

4.5 Temperature Monitoring

Use an infrared thermometer to scan key positions and establish summer temperature baseline data:

  • Main breaker terminals
  • Contactor terminals and contact area
  • Inverter heat sink
  • Heating circuit solid-state relays and contactors

For joints where the temperature difference between phases at the same position exceeds 10 °C, stop the machine to investigate the cause.

5. Emergency Handling

Fault Phenomenon

Possible Cause

Handling Measures

Inverter frequent overheating fault display

Heat sink blockage, fan stopped, or cabinet internal temperature too high

After shutdown, clean filter mesh, heat sink, and air ducts; check fan operating status.

PLC unresponsive or I/O module fault

Cabinet internal temperature exceeds allowable range

Install a temporary fan for forced ventilation cooling; restart after temperature returns to normal.

Main breaker tripping

Line overheating causing insulation breakdown, or loose terminal causing arcing discharge

Strictly prohibit direct reclosing; first investigate and eliminate the fault point, then restore power.

Smoke or burning odor inside cabinet

Connector overheating and melting

Immediately disconnect total power; use CO₂ or dry powder fire extinguisher to extinguish. NEVER use water.

 

6. Recommended Summer Spare Parts List

Spare Part

Recommended Qty

Purpose

Filter cotton

1 set per cabinet model

Regular replacement

Cabinet side cooling fan

1 each per model

Higher fan failure rate in high-temperature season

Common-spec contactor / relay

1 each

Quick replacement after contact burning

Terminal block

Several

Timely replacement when overheating discoloration is found

Desiccant pack

Several

Place inside cabinet for moisture absorption